Organised by symptom: find the symptom you are seeing, then work down the table.

This page is organised by symptom. Find the symptom you are seeing, then work down the table.

Nothing happens at all

SymptomLikely causeFix
No 5V LED on the boardNo mains, or the internal 5 V regulator has failedCheck the supply at J2. Check the mains fuse upstream of the board
The screen is completely darkThe screen has no 5 VCheck the screen cable at J5. The screen is powered from J5 pins 1–3
The screen is dark but the board's 5V LED is litThe screen's own timeout has switched the backlight offTouch the screen. If the timeout is too short, change Display timeout in Settings → Display Settings
The screen shows Check device connectionThe screen cannot reach the controller over its RS-485 linkCheck the screen cable at J5 (pins 4 and 5 carry the RS-485 pair). Check that the controller is powered

The controller is up but you cannot reach it

SymptomLikely causeFix
The web interface does not open at 192.168.1.195The address is different, or the network does not reach itRead the address from the screen: SYSTEM INFORMATION → NETWORK. Put your computer on the same subnet
The web interface does not open and the screen shows no addressThe unit has no network address at allCheck the Ethernet cable at J4 and the yellow link LED. If the yellow LED is dark, the cable or the switch is the problem
The yellow Ethernet LED is lit but the green one is darkThe link is running at 10 Mbit/sChange the switch port to 100 Mbit/s
The unit is not reachable after a DHCP changeThe address movedRead the address from the screen and reconnect. If DHCP does not answer, use a fixed address
Modbus/TCP does not answerThe Modbus port is not the default, or the ID does not matchCheck Modbus port and Modbus ID. The default is TCP 502 and ID 1
The RS-485 bus does not answerMissing termination, wrong baud rate, or the wrong node addressFit 120 Ω at both ends of the bus. Check RS485 baud rate and Modbus ID on every device
The RS-485 bus works with one device but not with severalThe bus is too long, or it is not a linear topologyKeep the bus linear, use twisted pair, and connect the common wire at every device
BACnet does not answerThe device ID is not unique, or the wrong port is usedCheck BACnet device ID. BACnet/IP uses UDP 47808 by default
The web interface rejects a valueThe value is outside the allowed rangeThe message names the fields that were rejected. Correct them and press Save again

The unit does not humidify

SymptomLikely causeFix
The mode stays StandbyNothing asked for AUTOMATICSet the mode to AUTOMATIC
The banner says Waiting: MasterThe master enable input is not activeCheck the wiring at J12 (MEn). The input reads as active when 24 V is present
The banner says Waiting: HygrostatThe hygrostat input is not activeCheck the wiring at J16 (HL_ONOFF) and the hygrostat itself
The banner says Waiting: AirflowThe airflow input is not activeCheck the wiring at J14 (Airflow) and that the fan is running
The banner says Waiting: Alarm <name>An alarm is blocking the runClear the cause, then acknowledge the alarm
The demand reads 0 %The demand source is wrong, or the signal is missingCheck Demand input mode against what is wired to J11. Check the wiring at the Input Signal row of the Inputs card
The demand reads 100 % in On/Off modeThe on/off input is activeCheck the wiring at J11
The demand does not follow the fieldbus registerThe demand source is not External demand registerSet Demand input mode to External demand register and write the demand register
The pump runs but no valve opensThe demand is above zero but the valve step settings exclude itCheck the valve step values. A valve whose lower level is equal to or above its upper level never opens
Only valves 3 and 4 are usedValves 1 and 2 are disabled, or their levels are wrongCheck the lower and upper level of each valve
The output drops to 0 % at high humidityThe limiter is workingThis is intended. The banner Output reduced due to Highlimit transmitter says so. Check the humidity in the supply air and the high-limit transmitter
The output is reduced and there is no bannerThe demand is genuinely lowCheck the demand source

Water problems

SymptomLikely causeFix
Water Pressure LowNo water, a closed valve, a blocked filter, or a leak before the pumpCheck the tank, the isolation valve and the filter between the tank and the pump
Water Pressure HighThe pump is not delivering: blocked filter, air lock, or a failing pumpCheck the filter and the pump
No Motor DriveThe pump is commanded on but the motor draws no currentCheck the motor, the wiring at J33, and the motor contactor. The alarm is checked while the pump runs, so it clears when the pump stops
Motor Temperature HighThe pump is blocked or overloadedCheck the pump and the water flow. The alarm clears when the motor cools down
Conductivity HighThe water is too conductiveCheck the water supply and the flushing interval
Conductivity After FlushThe conductivity stayed high for 2 minutes, or flapped 3 times in an hourFix the water supply, then acknowledge the alarm
Conductivity Sensor FaultThe probe at J37 is disconnected or unpoweredCheck the probe connector and the isolated 5 V LED (D38)
Water Temperature HighThe water supply is too hotCheck the water supply
Water Leak DetectedThe leak input has been triggeredClose the water supply, find the leak, fix it, then acknowledge the alarm
The unit flushes far more often than the intervalThe conductivity or the water temperature is out of rangeA flush is also triggered by Conductivity high and Water temperature high. Fix the water quality
The unit flushes and the demand stays at 0 %The flush holds the valve lock, so the demand controller waitsThis is intended; the unit resumes when the flush is finished

Alarms

SymptomLikely causeFix
An alarm comes back right after you reset itThe condition that caused it is still thereFix the cause first. The trip history is cleared when you reset, so the alarm latches again only if the condition returns
The alarm does not clear when I reset itThe alarm is not one that can be reset, or the condition persistsOnly the sticky alarms have a reset button. Check the alarm list in Status and alarms
Maintenance Required keeps coming backThe maintenance has not been acknowledgedWrite 1 to the MAINTENANCE register over the fieldbus, or press Reset on the Maintenance Required card on the screen
Input Signal ErrorThe demand input is carrying more voltage than it shouldCheck the signal source and the wiring at J11
Board Temperature HighThe controller is too hot inside its enclosureImprove the ventilation

Time and history

SymptomLikely causeFix
The clock is wrongThe clock has never been set, or the battery is flatSet the time on the screen or in the web interface. The clock is kept by a battery-backed cell (BT1)
The alarm history shows error for the dateThe clock was never set when the alarm was recordedSet the clock. Old entries keep their broken timestamps
The alarm history is emptyNothing has been logged yetAlarms are recorded as they happen
Failed to read alarm historyThe controller did not answerCheck the screen link at J5

The unit rebooted by itself

A reboot is usually a watchdog reset, or a power interruption. Check the Reboots counter in the System card: if it keeps growing, the unit is resetting on its own. Note the values on the screen and in the web interface before it goes down again, because the counter and the logs are the only record of what happened.

Collecting information before you call for help

  1. Note the serial number, the model and the firmware version. They are in the web interface footer and on the screen.
  2. Note the alarm list and the banner text.
  3. Note the address of the unit and the fieldbus settings.