Concepts
The handful of ideas you need in order to configure and troubleshoot an AdiaPure unit.
This page explains the handful of ideas you need in order to configure and troubleshoot an AdiaPure unit.
Demand
Demand is how much water the unit should put into the air, expressed as a percentage from 0 % to 100 %. The controller can take the demand from six different sources, chosen with the Demand input mode setting:
| Source | How it is measured |
|---|---|
0-10V demand | The voltage on the demand input, 0 V = 0 %, 10 V = 100 % |
4-20mA demand | The current on the demand input, 4 mA = 0 %, 20 mA = 100 % |
On/Off | The demand input is either 0 % or 100 % |
External demand register | A percentage written to a register over Modbus or BACnet |
Return humidity voltage | A 0–10 V return-air humidity signal, compared with a setpoint |
Return humidity current | A 4–20 mA return-air humidity signal, compared with a setpoint |
In the two return-humidity modes the demand is not read directly. Instead the controller
runs a closed loop: it compares the measured return humidity with the setpoint you gave it
and derives the demand from the difference. The loop runs on a fixed cycle
(PWM period, 10 s by default).
The limiter
The high-limit transmitter is a humidity sensor in the air leaving the humidifier. Its job is to stop the unit from humidifying so hard that water condenses inside the unit.
When the measured output humidity rises above the Highlimit transmitter threshold (60 % by default), the controller subtracts a penalty from the demand:
penalty = (measured output humidity - threshold) × gain
final demand = max(0, demand - penalty)The Highlimit transmitter gain (7.0 by default) sets how sharply the output is cut back. With the default gain, every 1 % of humidity above the threshold removes 7 % of the demand.
Two values are shown for the demand so you can see the limiter working:
| Web interface label | Meaning |
|---|---|
Demand (pre-limiter) | The demand as it arrived |
Demand (post-limiter) | The demand after the limiter has had its say |
On the screen, the banner Output reduced due to Highlimit transmitter appears while the
limiter is active.
Valves and the duty cycle
The unit has four atomisation valves. They are opened in stages, and each stage is controlled by pulse-width modulation: the valve is opened and closed repeatedly within a cycle, and the fraction of the cycle it stays open is the duty cycle.
Each valve has four settings:
| Setting | Meaning |
|---|---|
level_low | The demand at which this valve starts to open |
level_high | The demand at which this valve is fully open |
pwm_start | The smallest duty cycle this valve uses once it is active |
pwm_end | The largest duty cycle this valve uses |
Out of the box only the first two valves are enabled:
| Valve | level_low | level_high | Effect |
|---|---|---|---|
| Valve 1 | 10 % | 50 % | Starts working at 10 % demand, fully open at 50 % |
| Valve 2 | 50 % | 100 % | Starts working at 50 % demand, fully open at 100 % |
| Valve 3 | 0 % | 0 % | Disabled (the low and high levels are equal) |
| Valve 4 | 0 % | 0 % | Disabled |
A valve whose level_low is equal to or higher than its level_high never opens. That is
how you disable a stage, and it is also how the flushing routine knows to skip it.
The pump runs whenever the demand after the limiter is above zero. It is not switched off and on again for every cycle: if it would only be off for less than a second, the controller leaves it running.
Modes
The controller has three modes. You select them on the screen and in the web interface, and they are also readable and writable over the fieldbus.
| Mode | What it does |
|---|---|
STANDBY | Nothing runs. The pump is off and the valves are closed. This is the mode the unit starts in. |
AUTOMATIC | The unit follows the demand, but only when every enable condition is met. |
TEST | The unit runs at a fixed test demand, ignoring the enable conditions. It returns to STANDBY on its own when the test duration is over. |
What has to be true to run in AUTOMATIC
If any of these conditions fails while the unit is in AUTOMATIC, the pump and the valves
stop immediately. The screen shows which one is missing in the banner, for example
Waiting: Airflow.
In TEST mode the unit runs regardless of the master enable, the hygrostat, the airflow
and the alarms.
Mode changes
The test duration defaults to 1800 seconds (30 minutes). After that the unit returns to
STANDBY on its own.
Flushing
Atomisation valves must be flushed regularly, otherwise the nozzles clog and the water quality degrades. The controller runs a flush routine:
- the pump stops and all atomisation valves close;
- the flush drain valve opens;
- the controller waits 3 seconds;
- each enabled valve is opened in turn for
Flush duration(30 seconds by default), with a 3-second drain wait after each one; - the flush drain valve closes.
A flush is started when:
- the
Flush intervalhas elapsed (24 hours by default); - the water temperature or the conductivity has gone out of range;
- somebody asks for one (see Using the product).
A flush that is interrupted by an alarm closes all the atomisation valves first and leaves the flush drain valve open for 3 more seconds so the water can drain away.
Valves that are disabled (equal low and high levels) are skipped during the flush.
Alarms, and how they escalate
Alarms come in two flavours.
Transient alarms describe a condition that is happening right now. They clear automatically as soon as the condition goes away:
Water Temperature Too HighConductivity HighInlet Pressure Too LowPump Pressure Too LowMotor Temperature HighBoard Temperature HighConductivity Sensor Fault
Sticky alarms stay until you acknowledge them:
Water Temperature High— the water stayed too hot for long enoughConductivity After Flush— the water stayed too conductive for long enoughWater Pressure Low— the inlet pressure stayed too low for long enoughWater Pressure High— the pump pressure stayed too low for long enoughWater Leak DetectedNo Motor DriveMaintenance RequiredInput Signal Error
A transient alarm turns into its sticky counterpart in two ways:
- It persists. Water temperature and conductivity become sticky after 2 minutes; the two pressure alarms become sticky after 30 minutes.
- It keeps flapping. Water temperature and conductivity become sticky after 3 trips in one hour; the two pressure alarms become sticky after 10 trips in one hour.
That way a sensor that is only briefly out of range does not force an operator to acknowledge anything, but a genuinely broken sensor does.
Two alarms never clear by themselves at all: Water Leak Detected and Input Signal Error. Both need a manual reset.
See Status and alarms for the full list.
Maintenance countdown
The controller counts two things:
- Pump hours — the number of hours the pump motor has been running.
- Maintenance countdown — a one-year countdown to the next maintenance.
When the countdown reaches zero, or when more than 2000 pump hours have passed since the
last maintenance, the alarm Maintenance Required is raised.
Acknowledging the maintenance (writing the maintenance register) resets the pump-hours counter and restarts the one-year countdown. The web interface shows the remaining pump hours and the remaining countdown in the Maintenance card.
Relay outputs
Four relay outputs report the state of the unit:
| Output | Active when |
|---|---|
Status | There is a demand and the demand controller is running |
Alarm | At least one alarm is active |
Aux 1 | Any alarm in the Aux 1 alarm mask is active |
Aux 2 | Any alarm in the Aux 2 alarm mask is active |
Each output can be set to rest open (Normally Open) or rest closed (Normally Closed).
With the default Normally Open setting the contact is open while the output is inactive
and closed while it is active; with Normally Closed it is the other way round.
The valve lock
Only one part of the system may command the valves at a time. When the flushing routine
runs it takes the valve lock, and the normal demand controller waits until it is
released. You can see the lock state as Valve lock over the fieldbus.
Next steps
- Using the product — everyday tasks.
- Settings reference — every setting and its range.
- Status and alarms — the full alarm list.