AdiaPure

Hardware reference

Pinouts, link positions, indicator meanings and electrical specifications of the AdiaPure controller board, revision v0.3.

This page has the pinouts, the link positions, the indicator meanings and the electrical specifications of the AdiaPure controller board, revision v0.3.

How the board is labelled

The reference designator is printed on the board next to each part, for example J12 or K1. Those are the identifiers used throughout this documentation.

The functional name — what the terminal is for, such as MEn or Klep1 — is not printed. It exists only in the schematic, and this documentation gives it in brackets, for example J12 (MEn).

So you can find the terminal you want by its designator, and this page tells you what it is for. The wiring table in Installation and wiring is the full terminal map.

A few small parts are not marked on the board at all, so that the board stays uncluttered. They are all passives and none of them is a terminal you connect a field cable to.

Power

ItemValue
SupplyMains, into J2
Internal 24 V moduleIRM-30-24, described in the design data as 31.2 W, 24 V, 1.3 A
Internal 5 V regulatorTPS54331DR, with L1 (33 µH) and F2
Internal 3.3 V regulatorAZ1117CH-3.3TRG1, 1.35 A, with F1
Low-voltage fusesF1 (3.3 V), F2 (5 V)
Earth to signal groundNot bonded anywhere in the design. H1 and H2 are on Earth, H3–H5 are on the signal ground

Connector pinouts

Mains input

TerminalPinFunction
J2 (Mains)1–2Neutral
3–4Line
5–6Earth

Mains valve outputs

Each of these three-pole terminals carries: pin 1–2 = the switched leg, pin 3–4 = line, pin 5–6 = earth. Five of the seven are fitted on this revision.

TerminalSchematic nameDriven by the firmware as
J28Klep1Atomisation valve 1
J25Klep2Atomisation valve 2
J26Klep3Atomisation valve 3
J27Klep4Atomisation valve 4
J31Klep5Flush drain valve

Mains motor output

TerminalPinFunction
J33 (Motor)1–2Neutral
3–4Switched line
5–6Earth

24 V relay outputs (dry contacts)

TerminalSchematic nameOutput
J21StatusStatus relay
J22AlarmAlarm relay
J23AUX1Auxiliary 1 relay
J24AUX2Auxiliary 2 relay

Each is a two-terminal block carrying one potential-free contact. The board applies no voltage to these terminals. The contact's idle position is set by the wiring; the Normally Open / Normally Closed setting decides whether the relay is energised when the output is active or when it is idle.

24 V digital inputs

TerminalSchematic namePin 1Pin 2Link
J12MEn+24 VSignalJ13 (JP3)
J16HL_ONOFF+24 VSignalJ17 (JP1)
J14Airflow+24 VSignalJ15 (JP2)
J18Flush+24 VSignalnone
J19TempMotor+24 VSignalJ20 (JP1)

All five inputs are galvanically isolated from the controller's own electronics by an optocoupler, and all five read as active when 24 V is present on the signal pin.

Water leak input

TerminalSchematic namePin 1Pin 2Pin 3Pin 4Link
J7Waterlek+24 V0 V+24 VSignalJ8 (JP2)

Analogue inputs

TerminalSchematic namePin 1Pin 2Pin 3
J11Demand_IN+24 V (isolated)Signal0 V (isolated)
J34VD+5 V (isolated)0 V (isolated)Signal
J35HD+5 V (isolated)0 V (isolated)Signal
J9HR Transmitter+24 V (isolated)4–20 mA signal—

Analogue output

TerminalPinsFunction
J361–24–20 mA output, a two-wire loop. The transmitter takes its supply from the loop, so an external supply (typically 24 V) must be fitted across the two pins

Sensors and probes

TerminalSchematic namePin 1Pin 2Pin 3Pin 4Pin 5
J10Pulse_WC+5 VPulse signal0 V——
J37unnamedYx-1ElectrodeTemp-1Electrode0 V (isolated)

Communication ports

TerminalSchematic namePinsFunction
J4RJHSEN3848P8CEthernet, with magnetics and two LEDs
J6unnamed1: 0 V · 2: Mod- · 3: Mod+Fieldbus RS-485
J58P8C1–3: +5 V · 4: Scr- · 5: Scr+ · 6–8: 0 VScreen link (RS-485)
J32GT-USB-7055BBUSB-CService port: Modbus, and the firmware update connection. Device (USB 2.0) only - the controller cannot act as a USB host

The board has five two-pin links. Each one connects the signal pin of a 24 V input to the board's 24 V rail, which forces that input permanently active.

LinkSchematic nameInput it holds high
J13JP3J12 (MEn)
J17JP1J16 (HL_ONOFF)
J15JP2J14 (Airflow)
J20JP1J19 (TempMotor)
J8JP2J7 (Waterlek)

Each link sits next to the input it holds high, so you can tell them apart by position.

They are a commissioning aid: fit a link to hold an input active without cutting the field cable and placing a bridge across the input. Remove the link again for normal operation, so that the input follows the field wiring.

The Flush input (J18) has no link.

Indicators

Every indicator on the board is a yellow 0805 SMD LED (KT-0805Y), except the two LEDs built into the Ethernet connector.

The names in the second column come from the schematic. On the board, an LED is marked with its reference designator.

LEDSchematic nameLit when
D35VThe 5 V rail is present
D385VThe isolated 5 V rail is present
D19AlarmThe alarm output is active
D20StatusThe status output is active
D21AUX1Auxiliary output 1 is active
D22AUX2Auxiliary output 2 is active
D30Klep1The Klep1 output is driven
D31Klep2The Klep2 output is driven
D32Klep3The Klep3 output is driven
D33Klep4The Klep4 output is driven
D34Klep5The Klep5 (flush drain) output is driven
D45MotorThe motor output is driven

The Klep* and Motor LEDs mirror the relay drive, so they light when the corresponding output is switched on — even when no valve or motor is actually connected.

Ethernet connector LEDs

LEDColourBehaviour
YellowLED_YLit when the Ethernet link is up; blinks when there is traffic
GreenLED_GLit when the link runs at 100 Mbit/s; off at 10 Mbit/s

Electrical characteristics

Only values that the design data states are listed here.

Relay contacts

RelayUsed forPartStated rating
K1–K4Status, Alarm, Aux 1, Aux 2Omron G5V-1 (24 V DC coil, 6.25 mA)1 A at 30 VDC, 0.5 A at 125 VAC (at 40 °C); carry current 2 A; maximum switching 125 VAC / 60 VDC
K5–K8, K11The five fitted mains valve outputsFinder 34.51 / 93.11 (24 V DC coil, 170 mW)6 A rated, 10 A peak; 250 V AC rated, 400 V AC maximum switching; 1500 VA resistive load; 300 VA at 230 V AC inductive load; 0.185 kW single-phase motor at 230 V AC
K12The motor outputFinder 97.11Not stated in the project data

The Status, Alarm and Aux relays are low-current signal relays. Do not use them to switch mains.

RS-485

ItemValue
TransceiverSN75176BDR
Bias resistors560 Ω (R32–R35)
TerminationNo termination resistor is fitted on the board. Fit a 120 Ω resistor across the bus at each end of the bus
Surge protectionSM712 TVS diode array on each bus
Connection fault protectionPolyfuse on each bus line (F3–F6)

Analogue input ranges

SignalRange the controller expects
Demand input, voltage0–10 V
Demand input, current4–20 mA
Return humidity transmitter0–10 V or 4–20 mA
Inlet and pump pressure0–10 V

Analogue output

SignalRange
4–20 mA output4–20 mA over the full 0–100 % of the selected signal
Loop supply for the 4–20 mA output7.5–36 V (24 V typical), taken from the loop itself

Pressure signals on the 4–20 mA output are scaled over 0–20 bar.

Protection

ItemPart
USB ESD protectionUSBLC6-4SC6
RS-485 surge protectionSM712
Analogue input surge protectionSMAJ33CA TVS diodes
Analogue input connection protectionMF-USMF005-2 resettable fuses
USB VBUS protectionSP0503BAHT

Isolation

CircuitIsolation device
The analogue input front end (demand, return humidity, pressures)ADUM5411: isolated power for the ADC, and a digital isolator that carries all four SPI lines to the AD4111
The conductivity probeADUM5000ARWZ isolated power and ADuM1250 isolated I2C
The 24 V digital inputsEL357N optocouplers, 3750 V rms isolation
The motor current measurementTMCS1107A1BQDRQ1 hall sensor, isolated, 420 V working voltage
The Ethernet portNot isolated - the magnetics in the connector provide no galvanic barrier to the controller's ground

Next steps